VT Style: TYD500/√3-0.005H
Rated voltage: 500/√3kV
Highest voltage:550kV
No of core: 2
Rated Primary Voltage:
500/√3kV
Rated secondary voltage: 115.5/64.2, 115.5/64.2kV
Accuracy lass/Rated output:
0.2/0.2, 400/400 VA
Total simultaneous burden: 400VA
Thermal limiting output:1500VA
Frequency: 50Hz
Rated capacitance:5000pF
Insulating material: Oil
Service condition: outdoor
Insulation level: 550/830/1800/1300kV
Creepage Distance:17050mm
Ambient temperature: -25/+45℃
Over voltage capability:1.2 continue 1.5Un/30s.
Altitude: ≤1000m